Structure: composed mainly of glass fiber reinforced plastic sleeve, high temperature liquid silicone rubber (LSR) sheds and alloy flange.
Features:
1) Made of non-brittle materials with excellent explosion-proof property;
2) Excellent hydrophobic of LSR will result in almost no maintenance;
3) Strongly resistant to leakage tracking (4.5 kV) and galvanic corrosion;
4) Small weight and excellent seismic performance, easy for transportation and installation;
5) Long service life, stable and reliable quality and short delivery time.
35kV-1200kV AC Composite Hollow Insulator
Type
|
35
|
66
|
110
|
220
|
330
|
400
|
500
|
750
|
1100
|
1200
|
Rated highest voltage (kV)
|
40.5
|
72
|
126
|
252
|
363
|
440
|
550
|
800
|
1100
|
1200
|
Wet power frequency short-time withstand voltage (kV)
|
95
|
200
|
230
|
460
|
510
|
680
|
740
|
960
|
1200
|
1300
|
Wet switching impulse withstand voltage (kV)
|
/
|
/
|
/
|
/
|
950
|
1150
|
1234
|
1550
|
1800
|
2000
|
Full-wave lightning impulse withstand voltage (kV)
|
200
|
350
|
550
|
1050
|
1175
|
1550
|
1675
|
2100
|
2800
|
2800
|
Creepage distance (mm)
|
1260
|
2232
|
3906
|
7812
|
10845
|
13195
|
17050
|
26000
|
34100
|
37600
|
Dielectric dissipation factor tgδ
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
<0.005
|
Partial discharge (pC)
|
<5
|
<5
|
<5
|
<5
|
<5
|
<5
|
<5
|
<5
|
<5
|
<5
|
Anti-seismic strength
|
9
|
9
|
9
|
9
|
9
|
9
|
9
|
9
|
9
|
9
|
* All dimensions are for reference only; all the products can be designed and produced according to client’s demands.
±400kV-±1100kV DC Composite Hollow Insulator
Type
|
±400kV
|
±500kV
|
±600kV
|
±800kV
|
±1100kV
|
Rated highest voltage (kV)
|
412
|
515
|
680
|
824
|
1100
|
Wet power frequency short-time withstand voltage (kV)
|
570
|
680
|
750
|
1224
|
1300
|
DC withstand voltage (60 min)
|
680
|
780
|
1020
|
1224
|
1700
|
Wet switching impulse withstand voltage (kV)
|
1175
|
1380
|
1800
|
1800
|
2150
|
Full-wave lightning impulse withstand voltage (kV)
|
1234
|
1450
|
1950
|
2400
|
2750
|
Partial discharge (pC)
|
<5
|
<5
|
<5
|
<5
|
<5
|
Creepage distance (mm)
|
20600
|
24720
|
34000
|
43200
|
62720
|
Rated bending load (kN·m)
|
32
|
43
|
57
|
108
|
122.4
|
Ultimate bending load (kN·m)
|
≥80
|
≥108
|
≥142
|
≥270
|
≥550.8
|
* All products can be designed and produced according to client’s demands.
Product application: