HOME >> PRODUCT >> RIP Dry-type Condenser Bushing
40.5kV – 550kV Oil-air dry-type condenser transformer/reactor bushing
  • Description
  • Parameter

Product use:RIP condenser transformer/reactor bushings are mainly used in power transformers/reactors, working as the current carrying conductors for pulling in or drawing high, medium and low voltage side current of transformers/reactors, and playing a role of insulation for oil tank shell of transformers/reactors.

Service conditions

· Altitude: 1000m (products can be designed according to altitude correction coefficient if  altitude is higher than 1000m)

· Ambient air temperature: -45℃- +60℃

· Installation angle: arbitrarily

Product structure it is mainly composed of conducting pole, RIP capacitor core, high temperature liquid silicone rubber composite external insulation, equalizing ball, test tap, fittings, etc.

 

Advantages of bushings

Ø Unique resin system and special buffer strips

Ø The most advanced production equipment of the world guarantee the better electrical properties, heat-resistance and mechanical properties of RIP bushings series.

Ø The lower weight and smaller volume make it easy for transportation, erection and maintenance.

         Ø Oil-free and gas-free design is more environmentally friendly, no risk of explosion

 

    Ø Excellent performance ensures long-term stable online operation.

Description of product type

a Product type code

· BRFG Composite insulated RIP condenser transformer bushing

·BRCG Porcelain insulated RIP condenser transformer bushing

·BRQG Oil- SF6 RIP condenser transformer bushing

·BROG Oil- oil RIP condenser transformer bushing

· CRFG Composite insulated RIP condenser wall bushing

·CRCG Porcelain insulated RIP condenser wall bushing

· DRFG Composite insulated RIP condenser generator bushing

·GRFG Composite insulated RIP condenser GIS outlet line bushing

b Structural features code

 L  means it can be equipped with current transformers; no L means it can not be equipped with current transformers.

c Classification code

DC bushings are indicated with the letter Z; AC bushings are not expressed.

d Way of current carrying

 1-Direct type;2-Cable through type

 

TableⅠ Electrical performance table of oil - air dry-type condenser transformer/reactor bushings

Systemic nominal voltage Un  kV

35

66

110

132

150

220

330

420

500

Rated voltage Ur  kV

40.5

72.5

126

145

170

252

363

420

550

Maximum working phase voltage for equipment  Ur/  kV

23.5

42

73

84

98.5

146

210

242

317

60s Power frequency withstand voltage

Dry  kV (r.m.s)

95

155

255

305

355

505

625

695

870

Wet  kV(r.m.s)

80

140

230

275

325

460

535

680

790

Lightning impulse withstand voltage

Full wave kV (peak)

200

325

550

650

750

1050

1175

1425

1800

Chopped wave  kV (peak)

-

-

635

750

865

1210

1495

1639

2070

Switching impulse withstand voltage (dry or wet)  kV (peak)

-

-

-

-

-

850

950

1050

1300

Dielectric loss %

Added value (not more than)

1.05Ur/ - Ur: 0.1

Maximum value

40.5kV - 363kV

0.6, measured at the voltage of 1.05Ur/

420kV - 550kV

0.5, measured at the voltage of 1.05Ur/

Partial discharge at the voltage of Ur (not more than)   pC

10

Schematic diagram of  72.5kV and 126kV dry-type condenser transformer bushing 

 

 

Main dimensions of 72.5kV and 126kV dry-type condenser transformer bushings

                                                                                                                                        Unit:mm

Schematic diagram of  145kV and 170kV dry-type condenser transformer bushing

 

 

 Main dimensions of 145kV and 170kV dry-type condenser transformer bushings

                                                                                                                                            Unit:mm

Schematic diagram of  252kV and 550kV dry-type condenser transformer bushing

 

Main dimensions of 252kV dry-type condenser transformer bushings

                                                                        Unit:mm

 

 

Main dimensions of 550kV dry-type condenser transformer bushings

                                                                                                                                          Unit:mm

    
HOME   |   ABOUT   |   NEWS   |   PRODUCT   |   PROJECT   |   CONTACT
Copyright: Shandong Peiport Electric Power Science &Technology Co., Ltd Lu ICP Bei 05024719